Hydrocal 1003/1005

Hydrocal 1003/1005

 
HYDROCAL-1003

PURPOSE

Monitoring system SMT-EE is designed for transformer on-line diagnostics. It consists of Hydrocal device for gas-in-oil and moisturein-oil measurements, ZVCM 1001 device for bushings monitoringand SMT software for data visualization and processing. Additional signals from temperature sensors and current transformers could be use in system, what allows calculation of hot-spot and insulation ageing rate.

DESCRIPTION

Hydrocal 1003-1005 (MTE Meter Test Equipment, Switzerland) - Intelligent system for the individual measurement of dissolvedgas in oil contents:

[su_list icon="icon: bolt" icon_color="#004075"]
  • hydrogen (H2) and carbon monoxide CO – model 1003
  • hydrogen (H2), carbon monoxide CO, acetylene (C2H2),ethylene (C2H4) – model 1005
[/su_list]

and moisture (H2O) in the insulating oil of power transformers. Hydrocal is mounted on a valve on the transformer tank,without necessity of transformer switch-off.

Graphical firmware Hydrosoft enables Hydrocal parameters setting and data reading from memory. Hydrocal is equipped with communication interfaces for connection with external systems.

Software associated with Hydrocal 1003/1005 system allows:

[su_list icon="icon: bolt" icon_color="#004075"]
  • on-line, remote monitoring of all measured values,
  • trends of gas-in-oil and moisture content,
  • notifying user in case of alarm (by SMS too),
  • communication with external SCADA systems.
[/su_list]

 

TECHNICAL DATA

Measured concentrations: Hydrocal 1003 Hydrocal 1005
Hydrogen H2 0 ppm … 2.000 ppm ± 15 % of the measuring value ± 25 ppm 0 ppm ... 2.000 ppm ±15% ± 25 ppm
Carbon monoxide CO 0 ppm ... 2.000 ppm ± 20 % of the measuring value ± 25 ppm 0 ppm … 2.000 ppm ±20% ± 25 ppm
Moinsture-in-oil H2O absolute 0 ppm … 100 ppm, ± 3 % of the measuring value ± 3 ppm Absolute 0 ppm … 100 ppm ±3% ± 3 ppm
Acethylene C2H2    0 ppm … 2.000 ppm ±20% ± 5 ppm
Ethylene C2H4    0 ppm … 2.000 ppm ±20% ± 10 ppm
Operation temperature Oil Temperature: -20 °C ... +90 °C
Ambient temperature: -50 °C ... +55 °C

Oil Temperature: -20 °C ... +90 °C
Ambient temperature: -50 °C ... +55 °C

Analogue outputs (4…20 mA) 3 x analogue outputs: 4-20 mA (H2, CO, H2O concentration)
1 x analogue outputs: 4 ... 20 mA (free configurable)
5 x analogue outputs (H2, C2H2, C2H4, CO, H2O, configurable)
Digital outputs 4 x 12 V relay outputs (20 V DC / V AC, 2A, 60 W)
8 x opto-coupler outputs
5 x 12 V DC-relay outputs
5 x 5 V DC opto-coupler outputs
Analogue inputs: 4 x analogue DC inputs: 0/4 ... 20 mA
4 x analogue inputs: 0/4 ... 20 mA / 0 ... 10 V (configurable by jumpers)
4 x analogue DC inputs: 0/4 ... 20 mA
6 x analogue AC inputs: 0 ... 80 V +20%
Communication RS-232, RS-485, internal on-board modem (GSM 14.4 kBit / analogue 56 kBit) RS-232, RS-485, Ethernet (copper-wired or fibre optical)
Protection class IP 55  IP 55
Power supply 110 V / 230 V ± 20 %, max. 350 VA, 50/60 Hz 110 V / 230 V ± 20 %, max. 350 VA, 50/60 Hz
Wymiary: 215 x 215 x 215 mm 263 x 263 x 257 mm
Masa: about 8 kg  about 9 kg

  

All questions should be directed to:

  • mgr inż. Jerzy Buchacz, This email address is being protected from spambots. You need JavaScript enabled to view it.32 237 66 30

Dane kontaktowe

Zakład Pomiarowo-Badawczy Energetyki
"ENERGOPOMIAR-ELEKTRYKA"
Spółka z ograniczoną odpowiedzialnością
ul. Świętokrzyska 2, 44-100 Gliwice
woj. śląskie, Polska

(+48) 32 237 66 03 (sekretariat)

(+48) 32 237 66 15 (centrala)

(+48) 32 231 08 70 (fax)

Nasze wyróżnienia

gazela2010

gazela2009

gazela2008

 

UE ŚCP Europejskie Fundusze Strukturalne

UE Program Operacyjny Inteligentny Rozwój