PF-3 - 3 Phase Relay Test Set

PF-3 - 3 Phase Relay Test Set

PF-3-prawy
PF-3-pyta-czoowa
PF-3-lewy
PF-3-front
PF-3-front-nieaktualne

PURPOSE

3 Phase Injection test set PF-3 is designed to test protection relays by injection and shifting voltage, current and phase angle.

DESCRIPTION

  • The PF-3 generates sinusoidal waveforms with a frequency adjustable from 45Hz to 55Hz.
  • The voltage and current outputs generate three-phase signals with an angle shift between phases of 120° and star connection.
  • Phase regulation is set between voltage and current angle (device measures the angle between the first voltage phase and the first current phase).

TECHNICAL SPECIFICATION

Current output range
3 x up to 2 A
3 x up to 20 A
Current Burden
up to 40 VA
Voltage output range
3 x up to 120 V
Voltage Burden
up to 40 VA
Angle adjustment range
0 ÷ 360°
Frequency adjustment range
from 45 up to 55 Hz each 0,1 Hz
Voltage Inaccuracy
±(1 % w.w. + 1c)
Current Inaccuracy
±(1 % w.w. + 1c)
Angle Inaccuracy
±(1° + 1c)
Time Inaccuracy
±(0,01 % w.w. + 1c)
Frequency Inaccuracy
±(0,05% w.w.)
Operating Temperature
0 ÷ 40° C
Dimensions 650 x 450 x 220 mm
Weight ap. 24 kg

Technical support:

  • mgr inż. Dariusz Janecki, This email address is being protected from spambots. You need JavaScript enabled to view it.+48 32 237 66 73.

 

 

Dane kontaktowe

Zakład Pomiarowo-Badawczy Energetyki
"ENERGOPOMIAR-ELEKTRYKA"
Spółka z ograniczoną odpowiedzialnością
ul. Świętokrzyska 2, 44-100 Gliwice
woj. śląskie, Polska

(+48) 32 237 66 03 (sekretariat)

(+48) 32 237 66 15 (centrala)

(+48) 32 231 08 70 (fax)

Nasze wyróżnienia

gazela2010

gazela2009

gazela2008

 

UE ŚCP Europejskie Fundusze Strukturalne

UE Program Operacyjny Inteligentny Rozwój