TP-100/TP-200 Current transformer testing device

TP-100/TP-200 Current transformer testing device

TP-100-v2---prawy
TP-100-v2---pyta-czoowa-v2
TP-100-v2---lewy
TP-100-v2---front
TP-100bok-2

PURPOSE

Instrument transformer tester TP-100 is designed for checking of instrument transformers operating in semi-indirect and indirect systems used for making energy accounts. Checking should be done in the case of:

  • carrying out acceptance, start-up, service and post-accident tests,
  • when instrument transformer is damaged or verification marks are damaged or when both sides find erroneous indications or when the correct ratio is unknown (lack of rating plates).

Besides, tester can be used for checking and regulation of protection automatics components supplied from AC voltage source, as switches, current and voltage relays, overcurrent and thermal releases etc.

DESCRIPTION

Instrument transformer tester enables:

  • determination of angle uncertainty, current and real ratio and load of instrument transformer secondary side,
  • determination and regulation of operation threshold in current and voltage release of switch,
  • determination of time-current characteristic of overcurrent and thermal protection,
  • determination of self times of switches and contactors,
  • controlling and setting of other elements of protection automatics depended on current and voltage value,
  • data archiving, analysis and transfer to computer.

 

TECHNICAL DATA

Power supply 230 V , 50 Hz
Max. power consumption about 650 VA
Max. power of current output IPRI 600 VA
Current regulation range IPRI 0 ÷ 120 A
Current range ISEC 0 ÷ 10 A
Voltage range USEC 0 ÷ 100 V
Current source operation time IPRI for current up to 100 A continuous
Output voltage regulation range U for load current I 0 ÷ 0,5 A 0 ÷1000V
Allowable uncertainty of current and voltage measurement ±(0,2 % of reading + 2 digits)
Chronograph range 0 ÷ 100 h
Operation temperature -5*C do +40*C
Humidity up to 80%
Dimensions (width. x lenght x height) w mm 480 * 390 * 190mm
Weight about 25 kg

 

All questions should be directed to:

  • mgr inż. Zygmunt Pilny, This email address is being protected from spambots. You need JavaScript enabled to view it.32 237 66 70

Dane kontaktowe

Zakład Pomiarowo-Badawczy Energetyki
"ENERGOPOMIAR-ELEKTRYKA"
Spółka z ograniczoną odpowiedzialnością
ul. Świętokrzyska 2, 44-100 Gliwice
woj. śląskie, Polska

(+48) 32 237 66 03 (sekretariat)

(+48) 32 237 66 15 (centrala)

(+48) 32 231 08 70 (fax)

Nasze wyróżnienia

gazela2010

gazela2009

gazela2008

 

UE ŚCP Europejskie Fundusze Strukturalne

UE Program Operacyjny Inteligentny Rozwój