PURPOSE
Transformer Diagnostic Device type UDT-2 is appropriate for after-assembly, periodic and after-fault measurements of transformers, operating in power industry, according to Transformer Maintenance Manual (IET 2006), agreed with main transformer manufacturers and diagnostics companies in Poland.
Every UDT device is checked and certified by Measurement Devices Laboratory (accredited by PCA cert. no. AP 063). Measuring software is subjected to change in order to meet Customer needs, upgrades are periodically delivered to Customers.
DESCRIPTION
- Device components:
- mobile computer (notebook), connected with measurement cassette by USB interface,
- measurement cassette Euro3U, with galvanic separation 3 kV,
- current source for resistance measurement and OLTC tests,
- Windows XP system.
- Options and accessories:
- torque of motor driving OLTC measurement,
- cables with silicone insulation,
- transportation box,
- additional cables with terminals for simultaneous connection of all transformer phases.
- Software:
- designed for Windows XP system,
- co-operation with Excel spreadsheet, with automatic reporting,
- intuitive using of all measurement functions,
- Warranty service: 24 months,
- After-warranty service – with preference conditions.
TECHNICAL DATA
OLTC characteristic self-time measurement |
max. measurement duration time 300 s |
Exciting current measurement |
0 ÷ 100 mA AC |
Resistance measurement |
1 mΩ ÷ 100 Ω |
Regulating range of resistance measurement current |
0 ÷ 15 A DC |
Regulating range of resistance measurement voltage |
0 ÷ 30 V DC |
Transformer ratio measurement |
1/ √3 ÷ 50 |
Torque of motor driving OLTC measurement |
max. measured motor power 6 kW |
Operation temperature |
-5 °C ÷ +40 °C |
Power supply |
230 V, 50 Hz |
Dimensions |
560 x 420 x 170 mm (without transportation box) |
Weight | about 14 kg |